Abu Bakar, Norazhar and Abu-Siada, A. (2016) A Novel Method of Measuring Transformer Oil Interfacial Tension Using UV-Vis Spectroscopy. IEEE Electrical Insulation Magazine, 32 (1). pp. 7-13. ISSN 0883-7554
Text
A_novel_method_of_measuring_transformer_oil_interfacial_tension_using_UV-Vis_spectroscopy.pdf Restricted to Repository staff only Download (1MB) |
Abstract
A NOVEL TECHNIQUE FOR ESTIMATING THE IFTOF MINERAL TRANSFORMER OIL SAMPLES, USING UV-VIS SPECTROSCOPY IS DESCRIBE IN THIS PAPER. IT IS KNOWN THAT THERE IS A STRONG CORRELATION BETWEEN THE IFT OF THE OIL AND TWO OF ITS SPECTRAL RESPONSE PARAMETERS, NAMELY BANDWIDTH AND PEAK ABSORBANCE. TWO ARTIFICIAL INTELLIGENCE MODELS TO MAP THIS CORRELATION ARE DEVELOPED. THIS TECHNIQUE OFFERS THE ADVANTAGES THAT IT CAN BE USED ON SITE, DOES NOT NEED SPECIALLY TRAINED PERSONNEL TO MAKE THE MEASUREMENTS, HAS NEGLIGIBLE RUNNING COSTS, AND CAN BE READILY IMPLEMENTED ON-LINE FOR CONTINUOUS MONITORING OF THE CONDITION OF THE OIL.
Item Type: | Article |
---|---|
Uncontrolled Keywords: | Artificial neural network, Fuzzy logic, Interfacial tension, Transformer insulation oil, UV-Vis spectroscopy |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Faculty of Electrical Engineering |