Khallawi, Alaa Razzaq and Tan, Ying Yi and Hanaffi, Farhan and Abdul Razak, Hanim and Zainuddin, Hidayat and Chyad, Radhi Muhssin (2019) Transformer oil ageing detection using Mach-Zender interferometry configuration as a sensor. International Journal Of Recent Technology And Engineering (IJRTE), 8 (2S6). pp. 826-831. ISSN 2277-3878
Text
ALAA-IJRTE-PUBLISHED.PDF Download (930kB) |
Abstract
Paper In this paper, the fabrication and characterisation of an optical fibre sensor for transformer oil ageing detection are presented. Bare fibre is used in the Mach–Zender interferometry (MZI) configuration as a sensing arm. Hydrofluoric acid (30%) and a power meter are used in sensor fabrication. The MZI sensor is affected by the changes of the refractive index (RI) of the transformer oil. The sensor operates according to different output power levels at the receiving end of the optical sensor. Results agree with the AC breakdown voltage test and oil absorption spectrum test. This work contributes to the improvement of transformer oil monitoring systems by ensuring the availability of oil information and protecting such systems from damage
Item Type: | Article |
---|---|
Uncontrolled Keywords: | Transformer oil, Ageing measurement, Mach–zender interferometry, Bare fibre, Chemical etching |
Divisions: | Faculty of Electrical Engineering |
Depositing User: | Norfaradilla Idayu Ab. Ghafar |
Date Deposited: | 13 May 2022 16:34 |
Last Modified: | 25 May 2023 16:37 |
URI: | http://eprints.utem.edu.my/id/eprint/24387 |
Statistic Details: | View Download Statistic |
Actions (login required)
View Item |