Effect of repeated electrical breakdowns on mineral and natural ester insulating oils

Ab Ghani, Sharin and Ahmad Khiar, Mohd Shahril and Sutan Chairul, Imran and Zamir, Muhammad Imran (2021) Effect of repeated electrical breakdowns on mineral and natural ester insulating oils. Bulletin of Electrical Engineering and Informatics, 10 (6). pp. 2989-2996. ISSN 0208-9319

[img] Text
3258-7715-1-PB.PDF

Download (417kB)

Abstract

Transformer insulating oils are exposed to repeated electrical discharge or breakdowns inside power transformers. Durability tests are conducted to analyze the ability of oil to resist decomposition due to such high electrical stresses. With the increasing demand for alternative insulating oils for oilimmersed transformers, it is worthy to compare the performance of different types of insulating oils (conventional mineral-based insulating oil and natural ester-based insulating oil) under repeated electrical breakdown. In this paper, the AC breakdown voltage of different mineral-based and natural ester-based insulating oils is reported. Durability tests were conducted based on the AC breakdown voltage behavior of insulating oils after 50 electrical breakdown shots. The AC breakdown voltage of each insulating oil sample was assessed according to the ASTM D1816 standard test method. Based on the results, it can be concluded that the dissimilarity in chemical composition of the insulating oils has a significant effect on the AC breakdown voltage behavior of these oils under repeated electrical breakdowns.

Item Type: Article
Uncontrolled Keywords: Breakdown voltage, Durability, Mineral oil, Natural ester oil, Transformer oil
Divisions: Faculty of Electrical Engineering
Depositing User: Sabariah Ismail
Date Deposited: 22 Apr 2022 08:59
Last Modified: 22 Apr 2022 08:59
URI: http://eprints.utem.edu.my/id/eprint/25939
Statistic Details: View Download Statistic

Actions (login required)

View Item View Item