Planar sensor for noise cancellation during partial discharge detection in open substation

Kayser Azam, S. M. and Othman, Mohamadariff and Illias, Hazlee Azil and Abdul Latef, Tarik and Daniar Fahmi, Wan Nor Liza Wan Mahadi and Ain, Mohd Fadzil and Hossain, A K M Zakir (2023) Planar sensor for noise cancellation during partial discharge detection in open substation. IEEE Sensors Journal, 23 (14). pp. 15552-15562. ISSN 1558-1748

[img] Text
0261408122023465.pdf
Restricted to Registered users only

Download (2MB)

Abstract

In compliance with next-generation high-voltage substations, ultrahigh-frequency (UHF) planar sensors are becoming more popular than ever for their online features in partial discharge (PD) diagnostics. However, PD signals mixing with different noises still exist as a major challenge for UHF sensors. Especially in open substations, telecommunication interferences become predominant noise sources to an external UHF sensor placed outside of the equipment chamber. Even though band-stop filters are additionally connected to UHF sensors for denoising, the inherent noise cancellation mechanism is not yet found in any UHF sensor. With the best of our knowledge and survey, we are the first to introduce here a planar sensor that inherently eliminates telecommunication interferences during PD detection (PDD) for open substations even without using any postprocessing filters. To design our sensor, we have applied techniques of truncated partial ground plane for wideband characteristics and modified radiating patch for enhanced gain performance. A novel intermingled coupling resonator is designed to remove the GSM-900 band from within the sensor bandwidth. We have tested our prototype both for free-space propagation and PDD performances. The prototype has a compact physical size of 16 × 8 cm2 and an operational bandwidth of 792–1414 MHz. For a surface discharge source, the prototype successfully detects the PD signals at the earliest stage. Our prototype minimizes the ambient noise floor to 2.5 mV and improves the signal-to-noise ratio by more than 27.9 dB, which is relatively higher than conventional UHF sensors. The proposed sensor also has the potential of classifying PD sources.

Item Type: Article
Uncontrolled Keywords: Noise cancellation, Noise floor, Partial Discharge (PD) detection, Planar ultrahigh-frequency (UHF) sensor, Signal-to-noise ratio (SNR).
Divisions: Faculty of Electrical and Electronic Engineering Technology
Depositing User: Norfaradilla Idayu Ab. Ghafar
Date Deposited: 11 Apr 2025 11:21
Last Modified: 11 Apr 2025 11:21
URI: http://eprints.utem.edu.my/id/eprint/28654
Statistic Details: View Download Statistic

Actions (login required)

View Item View Item